EPSITRON® COMPACT Power
Device Description
29
787-1202 / -1212 / -1216 / -1226 EPSITRON® COMPACT Power
Manual
Version 1.0.0
Table 14: Environmental Conditions
Ambient operating temperature
T
A
-25 °C … +70 °C
1)
Storage temperature
-40 °C … +85 °C
Relative humidity
10 % … 95 %
Climatic category
3K3 (acc. to EN 60721, except for low air
pressure)
Elevation above sea level
≤
2000 m
1)
see section “Notes on Operation” > “Derating”
Pos: 35.7 /Serie 787 (
EPSITRON
)/Ger ätebeschrei bung/T echnische D aten/Ei nbaulagen 787- 12xx @ 18\mod_1393415700998_21.docx @ 146543 @ @ 1
Table 15: Mounting
Mounting options
•
on DIN 35 rail
•
Screw mount with fastening clips
(supplied)
Vertical mounting (front panel front)
Distance top/bottom/front
Distance left/right
70 mm
0 mm
Horizontal mounting (front panel top)
Distance front/bottom/top
Distance left/right
70 mm
20 mm
Horizontal mounting (front panel
bottom)
Distance front/back/bottom
Distance left/right
70 mm
20 mm
Other mounting positions on request
Pos: 35.8 /Serie 787 (
EPSITRON
)/Wichtige Erläuterungen/Sicher heits- und sonstige Hi nweise/Hi nweis/Hinweis: Bei Langzeitl ager ung beachten! @ 18\mod_1393415896066_21.docx @ 146547 @ @ 1
Observe for long-term storage!
For long-term storage, power must be applied to equipment with built-in
capacitors at least every two years for five minutes.
Pos: 36 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1