50
Notes on Operation
EPSITRON® COMPACT Power
787-1202 / -1212 / -1216 / -1226 EPSITRON® COMPACT Power
Manual
Version 1.0.0
Pos: 65 /All e Seri en (Allgemei ne Module)/Ü berschriften/N eue Ü berschriften/Ebene 2D erating - Ü berschrift 2 @ 19\mod_1399290806141_21.docx @ 152983 @ 2 @ 1
6.5
Derating
Pos: 66 /Serie 787 (
EPSITRON
)/In Betrieb nehmen/Der ati ng 787- 12xx @ 19\mod_1399295852460_21.docx @ 153006 @ @ 1
The maximum load is dependent on the ambient temperature and the input
voltage.
Table 28: Performance Data According to UL
787-1202
787-1212
787-1216
787-1226
U
IN
100 VAC … 240 VAC
P
OUT
100 VAC … 240 VAC
110 VAC … 240 VAC
31 W
48 W
60 W
48 W
60 W
48 W
60 W
T
A
+55 °C
Restrictions (derating) apply when the power supply unit is used in applications
that exceed its performance specifications; these are listed below:
Table 29: Deratings
Input voltages U
IN
Derating See figure
U
IN
< 140 VDC
-1,33 %/V “Input voltage load characteristic” >
“Input voltage [DC V]”
U
IN
< 100 VAC
-2 %/V
Input voltage load characteristic” >
“Input voltage [AC V] / 50 Hz”
T
A
> +55 °C
-2.66 %/K “Temperature load characteristic”
Figure 21: Input Voltage Load Characteristic
Figure 22: Temperature Load Characteristic
Pos: 67 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1