34 Function Description
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
6.5
ON Delay for Specific Channels
The channels are activated in a staggered manner in the order of their channel
numbers as soon as a minimum input voltage is present. All channels
deactivated manually or by a reset signal are skipped in this process.
The time at which the next channel in the sequence is activated is based on the
following conditions:
•
At least 50 ms must elapse after switching on the previous channel.
•
The output current of the previously activated channel must lie below the
nominal value set for the channel.