Connect Devices 39
787-2861 Electronic Circuit Breaker
Manual
Version 1.3.1
Pos: 67 /Serie 787 (EPSITRON)/Anschließ en/Brücken - 787- 2861 @ 25\mod_1455280178632_21.docx @ 201525 @ 2 @ 1
6.3
Bridging Voltage or Signal
Push-in type jumper bars can be used to distribute an applied voltage or signal to
several 787-2861 electronic circuit breakers.
•
Bridging the power supply:
The maximum supply current per connection point is 20 A. A current of
40 A can be distributed to multiple electronic circuit breakers if the potential
is supplied and bridged via two connection points in parallel.
•
Bridging signal output S2:
The signal outputs of up to 30 devices can be bridged and serve as a
common signal.
Figure 10: Push-in type jumper bars