WAGO Operating Instructions 4PU/4PS/2PU CT 25
Additional values and OBIS codes displayed in the Bluetooth® readout:
OBIS-Code
Content
OBIS-Code
Content
Active Energy [kWh]
Reactive Energy in quadrant 1 and 2 (Forward)
1.8.0
Forward Active Energy
5.8.0
Inductive Forward Reactive Energy Q1 (Total)
15.8.0
Total Active Energy
5.8.1
Inductive Forward Reactive Energy Q1 (T1)
15.8.1
Total Active Energy T1
5.8.2
Inductive Forward Reactive Energy Q1 (T2)
15.8.2
Total Active Energy T2
5.8.3
Inductive Forward Reactive Energy Q1 (T3)
15.8.3
Total Active Energy T3
5.8.4
Inductive Forward Reactive Energy Q1 (T4)
15.8.4
Total Active Energy T4
6.8.0
Capacitive Forward Reactive Energy Q2 (Total)
35.8.0
Total Active Energy L1
6.8.1
Capacitive Forward Reactive Energy Q2 (T1)
55.8.0
Total Active Energy L2
6.8.2
Capacitive Forward Reactive Energy Q2 (T2)
75.8.0
Total Active Energy L3
6.8.3
Capacitive Forward Reactive Energy Q2 (T3)
21.8.0
Forward Active Energy L1
6.8.4
Capacitive Forward Reactive Energy Q2 (T4)
41.8.0
Forward Active Energy L2
Reactive Energy in quadrant 3 and 4 (Reverse)
61.8.0
Forward Active Energy L3
7.8.0
Inductive Reverse Reactive Energy Q3 (Total)
2.8.0
Reverse Active Energy
7.8.1
Inductive Reverse Reactive Energy Q3 (T1)
22.8.0
Reverse Active Energy L1
7.8.2
Inductive Reverse Reactive Energy Q3 (T2)
42.8.0
Reverse Active Energy L2
7.8.3
Inductive Reverse Reactive Energy Q3 (T3)
62.8.0
Reverse Active Energy L3
7.8.4
Inductive Reverse Reactive Energy Q3 (T4)
Reactive Energy [kvarh]
8.8.0
Capacitive Reverse Reactive Energy Q4 (Total)
-
Total Reactive Energy T1
8.8.1
Capacitive Reverse Reactive Energy Q4 (T1)
-
Total Reactive Energy T2
8.8.2
Capacitive Reverse Reactive Energy Q4 (T2)
-
Total Reactive Energy T3
8.8.3
Capacitive Reverse Reactive Energy Q4 (T3)
-
Total Reactive Energy T4
8.8.4
Capacitive Reverse Reactive Energy Q4 (T4)
3.8.0
Forward Reactive Energy
Power Factor [cos
ɸ
]
3.8.1
Forward Reactive Energy T1
13.7.0
Power Factor
3.8.2
Forward Reactive Energy T2
33.7.0
Power Factor L1
23.8.0
Forward Reactive Energy L1
53.7.0
Power Factor L2
43.8.0
Forward Reactive Energy L2
73.7.0
Power Factor L3
63.8.0
Forward Reactive Energy L3
4.8.0
Reverse Reactive Energy
12.7.0
Voltage [V]
4.8.1
Reverse Reactive Energy T1
14.7.0
Frequency [Hz]
4.8.2
Reverse Reactive Energy T2
C.87.0
Active Tariff
24.8.0
Reverse Reactive Energy L1
44.8.0
Reverse Reactive Energy L2
64.8.0
Reverse Reactive Energy L3
Summary of Contents for 879-3000 4PU
Page 7: ...WAGO Operating Instructions 4PU 4PS 2PU CT 7 3 2 CE Declaration of Conformity 4PU und 4PS...
Page 8: ...8 WAGO Operating Instructions 4PU 4PS 2PU CT 3 3 MID Declaration of Conformity 2PU CT...
Page 9: ...WAGO Operating Instructions 4PU 4PS 2PU CT 9 3 4 CE Declaration of Conformity 2PU CT...
Page 18: ...18 WAGO Operating Instructions 4PU 4PS 2PU CT 6 4 Process Diagram 4PU 4PS 2PU CT...