34 WAGO Operating Instructions 4PU/4PS/2PU CT
A3.2 Modbus
®
Register Map
Reg. address Content
Function code Length
Unit
Data type
4000
Serial number
03
2
-
HEX
4002
Meter code
03
1
-
HEX
4PU: 1111 - 4PS: 1112 - 2PUCT: 1113
4003
Modbus ID
03
1
-
Signed
4004
Baud rate
03
1
-
Signed
1: 300 - 2: 600 - 3: 1200 - 4: 2400
5: 4800 - 6: 9600 - 7: 19200 - 8: 38400
9: 57600 - 10: 115200
4005
Protocol version
03
2
-
Float ABCD
4007
Software Version
03
2
-
Float ABCD
4009
Hardware version
03
2
-
Float ABCD
400B
Meter amp
03
1
A
Signed
400C
CT ratio
03
1
A
HEX
400D
S0 pulse rate
03
2
pulse/kW
h
Float ABCD
400F
Combinations code
03
1
-
Signed
1: import only - 2: export only
3: export - 4: import - export
5: import - export (10)
4010
LCD rolling time
03
1
sec.
HEX
4011
Parity
03
1
-
Signed
1: even - 2: none - 3: odd
4012
L1 current direction
03
1
-
ASCII
F: import - R: export
4013
L2 current direction
03
1
-
ASCII
F: import - R: export
4014
L3 current direction
03
1
-
ASCII
F: import - R: export
4016
Power-down counter
03
1
-
Signed
4017
Current quadrant
03
1
-
Signed
4018
L1 quadrant
03
1
-
Signed
4019
L2 quadrant
03
1
-
Signed
401A
L3 quadrant
03
1
-
Signed
401B
Checksum
03
2
-
HEX
401D
Active status word
03
2
-
HEX
401F
CT ratio
03
2
A
Signed
9995 005 = 9995/5
4021
S0 pulse width
03
2
ms
Signed
Value between 2-99 ms
4022
S0 pulse type
03
1
-
HEX
1: Active energy and reactive energy
2: import & export
4023
Checksum 2 (not relevant)
03
2
-
HEX
4025
Reserved for later adjustments
-
1
-
-
4026
Data type
03
1
-
Signed
1: Standard
–
2: Integer
Summary of Contents for 879-3000 4PU
Page 7: ...WAGO Operating Instructions 4PU 4PS 2PU CT 7 3 2 CE Declaration of Conformity 4PU und 4PS...
Page 8: ...8 WAGO Operating Instructions 4PU 4PS 2PU CT 3 3 MID Declaration of Conformity 2PU CT...
Page 9: ...WAGO Operating Instructions 4PU 4PS 2PU CT 9 3 4 CE Declaration of Conformity 2PU CT...
Page 18: ...18 WAGO Operating Instructions 4PU 4PS 2PU CT 6 4 Process Diagram 4PU 4PS 2PU CT...