38 WAGO Operating Instructions 4PU/4PS/2PU CT
6085
Export capacitive reactive energy in Q4 (T2) 03
2
kvarh
Float ABCD
6087
Export capacitive reactive energy in Q4 (T3) 03
2
kvarh
Float ABCD
6089
Export capacitive reactive energy in Q4 (T4) 03
2
kvarh
Float ABCD
608B
Resettable day register L1
03
2
kWh
Float ABCD
608D
Resettable day register L2
03
2
kWh
Float ABCD
608F
Resettable day register L3
03
2
kWh
Float ABCD
A3.3 Modbus
®
Write Register
Reg. address
Content
Function code
Length
Unit
Data type
4003
Modbus
®
ID
06
1
-
Signed
Command:
01 06 4003 000A (new ID: 10)
01~247 - 01 standard
–
00 broadcast
4004
Baud rate
06
1
-
Signed
Command:
01 06 4004 00 06 (new baud rate: 9600)
1: 300
–
2: 600 - 3: 1200
–
4: 2400
5: 4800
–
6: 9600
–
7: 19200
8: 38400
–
9: 57600
–
10: 115200
400D
S0 pulse rate
10
2
pulse/kW
h
Float ABCD
Command:
01 10 400D 0002 04 41 20 00 00 (new S0: 10)
10,000
–
2,000
–
1,000
–
100
–
10
–
1 0.1
–
0.01
400F
Combinations code
06
1
-
Signed
Command:
01 06 400F 0004 (new code: 4 F-R)
1: import only
–
2: export only
3: export; 4: import
–
export
5: import
–
export (10)
4010
LCD rolling time
06
1
Seconds HEX
Command:
01 06 4010 0025 (new time: 25 sec.)
01~30
4011
Parity
06
1
-
Signed
Command:
01 06 4011 0002 (new parity: none)
01: even
–
02: none
–
03: odd
4016
Power-down counter 06
1
-
Signed
Command:
01 06 4016 0000
Reset to 0
6048
Tariff
06
1
-
Signed
Command:
01 06 6048 0002 (new tariff: 2)
1: T1
–
2: T2 - 3: T3
–
4: T4
6049
Resettable day register
10
1
kWh
Float ABCD
Command:
01 10 6049 0002 04 0000 0000
Reset to 0
401F
CT ratio
2
-
Signed
Command:
01 10 401F 0002 04 9995 0005
Set to 9995/5
4021
Pulse width
06
1
ms
4021
Command:
01 06 4021 0030 (new width: 30ms)
2~99 ms
4022
Pulse type
06
1
-
4022
Command:
01 06 4022 0002
(new setting: import and export)
2 = forward & reverse
4026
Data type
06
1
-
4026
Command:
01 06 4026 0002 (new setting: integer)
1 = standard, 2 =
integer
4032
Screen direction
06
1
-
4032
Command:
01 06 4032 0001
(new setting: rotate 180°)
0: standard
–
1: rotated 180°
4033
OBIS code ON/OFF
06
1
0 = Signed
Command:
01 06 4033 0001 (new setting: OBIS ON)
0: OFF
–
1: ON
Summary of Contents for 879-3000 4PU
Page 7: ...WAGO Operating Instructions 4PU 4PS 2PU CT 7 3 2 CE Declaration of Conformity 4PU und 4PS...
Page 8: ...8 WAGO Operating Instructions 4PU 4PS 2PU CT 3 3 MID Declaration of Conformity 2PU CT...
Page 9: ...WAGO Operating Instructions 4PU 4PS 2PU CT 9 3 4 CE Declaration of Conformity 2PU CT...
Page 18: ...18 WAGO Operating Instructions 4PU 4PS 2PU CT 6 4 Process Diagram 4PU 4PS 2PU CT...