WAGO Gateway Installation and Service
Specifications
BACnet/IP to MS/TP Router Specification
(continued)
Dimensions
Webpage Configuration
The BASrouter contains an interactive web server
accessible from any Internet-compatible PC on the local
network with recent versions of most standard web
browsers such as Microsoft Internet Explorer, Microsoft
Edge, Mozilla Firefox, or Google Chrome installed. It is
factory-programmed with a default fixed IP address of
192.168.1.18 and a Class C subnet mask of
255.255.255.0 (/24). The default login credentials for the
web page are admin / Vimaster99.
The figure shows the setup for initial network configuration.
Using BASRT-B, a computer for configuration, and a
connection to the MS/TP network.
To configure the router, connect it to a computer with an
Ethernet cable and use a standard web browser.
For initial configuration, the PC chosen for the procedure
should temporarily have its IP address modified to match
the default subnet of the BASrouter and Wago gateway.
After successfully logging in, the main -
Router Configuration web page is loaded.
This page allows for setting up router parameters.
Reset IP Switch
The Reset IP switch is located on the front, underneath
RJ-45 connector. To reset the router to its default values
(except for configuration settings), press and hold the
Reset IP button using a paper clip for at least 3 seconds
while the router is powered. Remove power and restore
power again to complete the reset IP, User ID, and
Password procedure to factory-programmed default values
as shown below. Default User Name is admin and default
Password is admin.