11.2.2 Perform Firmware Update/Downgrade
Proceed as follows if you want to update the controller to a later firmware version
or to downgrade the controller to an earlier firmware version:
1.
Save your application and the controller settings.
2.
Switch off the controller.
3.
Insert the memory card with the new firmware image into the memory card
slot. Use a special downgrade image if necessary (see above).
4.
Switch on the controller.
5.
After booting the controller, launch the WBM “Create Boot Image” page
(you may have to temporarily change the IP address).
6.
Create a new boot image on the internal memory.
7.
Switch off the controller after completing the process.
8.
Remove the memory card.
9.
Switch on the controller.
The controller can now be started with the new firmware version.