4.3.13 Climatic Environmental Conditions
Table 30: Technical Data – Climatic Environmental Conditions
Surrounding air temperature (operation)
−25
… +60
°C
Surrounding air temperature (storage)
−
25 … +85
°C
Relative humidity (without
condensation)
5 … 95 %
Operating altitude above sea level
2000 m
Pollution degree
2
Overvoltage category
II
Protection type
IP20
Special conditions
• Ensure that additional measures for
components are taken, which are
used in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
• The permissible temperature range
of the connecting cable must be
dimensioned based on the
mounting position and current
intensity, as the temperature of the
terminal connection can be up to
25
°K above the maximum
expected surrounding air
temperature (at 10 A).
The permissible ambient temperatures in relation to the installation positions can
be found in section "Mounting" > "Installation Position".