92 Commissioning
WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
8.8.1
Configuration via Web-Based-Management (WBM)
The HTML pages (from here on referred to as “pages”) of the Web-Based
Management are used to configure the controller. Proceed as follows to access
the WBM using a web browser:
1.
Connect the controller to the ETHERNET network via the ETHERNET
interface X1.
2.
Start a Web browser on your PC.
3.
Enter “https://” followed by the controller's IP address and “/wbm-ng” in the
address line of your web browser, e.g., “https://192.168.1.17/wbm-ng”.
Note that the PC and the controller must be located within the same subnet
(see Section “Setting an IP Address”).
If you do not know the IP address and cannot determine it, switch the
controller temporarily to the pre-set address “192.168.1.17” (“Fixed IP
address” mode, see Section “Commissioning” > … > “Temporarily Setting a
Fixed IP Address”).
Take usage by the CODESYS program into account
If the controller is at capacity due to a CODESYS program, this may result in
slower processing in the WBM. As a result, timeout errors are sometimes
reported in some circumstances. It is therefore important to stop the CODESYS
application prior to performing complicated configurations using WBM.
When the connection has been established, a login window opens.
Figure 16: Entering Authentication
4.
Enter the username and password.
5.
Click the
[Login]
button.
6.
If you only want to log in as a guest, click the
[Guest]
button.