3.2.11 Technical
Data
System data
Max. no. of nodes
64 with scanner
Max. no. of I/O points
ca. 6000 (depends on master)
Transmission medium
shielded Cu cable,
trunk line: AWG 15, 18 (2x 0.82mm
2
+2x1.7mm
2
)
drop line: AWG 22, 24 (2x0.2mm
2
+2x0.32mm
2
)
Max. length of bus line
100 m ... 500 m
(baud rate dependent / cable dependent)
Baud rate
125 kBaud, 250 kBaud, 500 kBaud
BusCoupler connection
5-pole male connector, series 231 (MCS)
female connector 231-305/010-000/050-000
is included
Programming
WAGO-I/O-PRO 32
IEC 61131-3
IL, LD, FBD, ST, FC
Standards and approvals
UL
E175199, UL508
E198726
Clas I Div2 ABCD T4A (applied for)
Conformity marking
CE
Accessories
EDS-Dateien
750-912
Miniature WSB quick marking system
Technical data
Max. number of I/O modules
64
Fieldbus
Input process image
max. 1024 Byte
Output process image
max. 1024 Byte
Input variables
max. 512 Byte
Output variables
max. 512 Byte
Program memory
128 kByte
Data memory
64 kByte
Non-volatile memory
8 kByte (retain)
Cycle time
< 3 ms for 1,000 statements /256 dig. I/Os
Configuration
via PC or control
DeviceNet features
Polled I/O Message Connection
Strobed I/O Message Connection
Change of State / Cyclic Message Connection
UCMM Device, expandable to master with De-
vNet.lib
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)