DeviceNet • 119
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
5.6.2.1.3 Message Router (0x02):
no attribute, no services
5.6.2.1.4 DeviceNet Object (0x03):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Default
Value
1
required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation
is based.
0x02
Instance 1:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Default
Value
1
Optional
get
MAC ID
USINT
Node address
0 - 63
2
Optional
get
Baud Rate USINT
Baud rate
0 - 2
3
Optional
get/set
BOI
BOOL
Bus-off Interrupt
0/1
4
Optional
get/set
Bus-Off
Counter
USINT
Number of times CAN went to
the bus-off state
0 - 255
5
Optional
get
Allocation
Informati-
on Allo-
cation
Choice
Byte
Master`s
ID
Struct of:
BYTE,
USINT
s. MAC ID of Master (from
Allocate)
0 - 63, 255
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute value
0x10
Set_Attribute_Single
Used to modify a DeviceNet object attribute value
0x4B
Allocate_Master/Slave_Connection
Requests the use of the predefined Master/Slave
connection
0x4C
Release_Group_2_Identifier_Set
Indicates that the specified connections within the
predefined Master/Slave connection set are no
longer desired. These connections are to be released
(deleted)
5.6.2.1.5 Assembly Object (0x04):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
0x01