52
• Fieldbus Coupler/Controller
Fieldbus Coupler 750-306
WAGO-I/O-SYSTEM 750
DeviceNet
2.
DIP switches 7 and 8 are used to set the desired baud rate.
Baud rate
DIP7
DIP8
125 kBaud
*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
12
34
5
ON
67
8
1
2
3
4
5
6
7
8
ON
g012541x
Fig. 3-11: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
*)
Presetting
3.
Then switch on the Coupler supply voltage.
3.1.7.3 Configuration with Static Assembly
In this example, the software WAGO
NETCON
is used for the configuration.
The node in the example consists of the following I/O modules:
750-306
402
DI DI DI DI DODO
402
516
516
516
467
550
600
1
2
3
4
5
6
7
8
DODO DODO AI AI AO AO
Fig. 3-12: Example for a fieldbus node
g012552x
1. Starting Software and EDS file load
1.
Start the configuration software WAGO
NETCON
.
2.
Load an EDS file for the fieldbus Coupler in WAGO
NETCON
, i. e.
"4.EDS".
For this click on "File/ Copy EDS" and choose the EDS-file to load.
Note
You can download the EDS files for the fieldbus Coupler from the Inter-
net under: www.wago.com.
Upon downloading the EDS file into WAGO
NETCON
, you can create a
new project and start configuring your network.