62
• Feldbus Coupler/Controller
Fieldbus Controller 750-806
WAGO-I/O-SYSTEM 750
DeviceNet
3.2.1 Description
The programmable fieldbus Controller 750-806 (short: PFC) combines the
DeviceNet functions of the fieldbus Coupler 750-306 with that of a program-
mable logic control (PLC).
The application program is created with
WAGO-I/O-
PRO
32
in accordance
with IEC 61131-3.
All input signals of the sensors are grouped in the Controller.
According to the IEC 61131-3 programming, data processing occurs locally in
the PFC. The link results created in this manner can be put out directly to the
actuators or transmitted to the higher ranking control system via the bus.
The programmer has access to all fieldbus and I/O data.
In the initialization phase, the fieldbus Controller determines the physical
structure of the node and creates a process image from this with all inputs and
outputs. This could involve a mixed arrangement of analog (word by word
data exchange) and digital (byte by byte data exchange) modules.
The local process image is subdivided into an input and output data area.
The data of the analog modules are mapped into the PDOs according to the
order of their position downstream of the bus Coupler. The bits of the digital
modules are compiled to form bytes and also mapped into PDOs. Should the
number of digital I/Os exceed 8 bits, the Coupler automatically starts another
byte.
In addition to the functions of the fieldbus Coupler, the fieldbus Controller
supports the following DeviceNet functions:
•
Create Connection via UCMM-Port
•
Offline Connection Set
•
DeviceNet Shutdown
•
Dynamic assembly
•
Change MAC ID by SW
•
Heartbeat
•
Bit-Strobe