Feldbus-Koppler/-Controller • 69
Fieldbus Controller 750-806
WAGO-I/O-SYSTEM 750
DeviceNet
3.2.2.8 Setting the Baud Rate
The fieldbus controller supports 3 different Baud rates, 125 kBaud, 250 kBaud
and 500 kBaud. DIP switches 7 and 8 are used to set the baud rate.
Baudrate
DIP7
DIP8
125 kBaud
*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
12
34
5
ON
67
8
1
2
3
4
5
6
7
8
ON
g012541x
Fig. 3-27: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) on a
station (node) with the address MAC
ID 1.
*)
Presetting
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the
buscoupler. Turn off and on the power supply for the fieldbus controller to ac-
cept the changing.
The default setting is Baud rate 125 kB.