Important Comments
•
7
Safety Notes
WAGO-I/O-SYSTEM 750
DeviceNet
1.5 Safety Notes
Attention
Switch off the system prior to working on bus modules!
In the event of deformed contacts, the module in question is to be replaced, as
its functionality can no longer be ensured on a long-term basis.
The components are not resistant against materials having seeping and insu-
lating properties. Belonging to this group of materials is: e.g. aerosols, sili-
cones, triglycerides (found in some hand creams).
If it cannot be ruled out that these materials appear in the component envi-
ronment, then additional measures are to be taken:
- installation of the components into an appropriate housing
- handling of the components only with clean tools and materials.
Attention
Cleaning of soiled contacts may only be done with ethyl alcohol and leather
cloths. Thereby, the ESD information is to be regarded.
Do not use any contact spray, as in a worst-case scenario; the functioning of
the contact area can be impaired.
The WAGO-I/O-SYSTEM 750 and its components are an open system. It
must only be assembled in housings, cabinets or in electrical operation
rooms. Access must only be given via a key or tool to authorized qualified
personnel.
The relevant valid and applicable standards and guidelines concerning the
installation of switch boxes are to be observed.
ESD
(Electrostatic Discharge)
The modules are equipped with electronic components that may be destroyed
by electrostatic discharge. When handling the modules, ensure that the envi-
ronment (persons, workplace and packing) is well grounded. Avoid touching
conductive components, e.g. gold contacts.