110 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
Table 82: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
11
specific
get/set
BK_FAULT_
REACTION
USINT
Enumeration for error handling
0: Stops local input/output
cycles (default)
1: Sets all outputs to 0
2: Does nothing
12
specific
get/set
BK_SEL_
STORED_POL
L_P_PATH
UINT
Power-up value for send path.
“Polled I/O” enumeration for the
assembly path, class and
instance for the object path.
(Notice:
e.g., do not choose analog inputs
if only digital input modules on
the node)
4: Analog/digital input data plus
status
5: Digital input data plus status
6: Analog input data plus status
7: Analog/digital input data
8: Digital input data
9: Analog input data
12: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45)
13: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45) plus
BK_LED_ERR_ARG (C 100, I
1, A46)
14: Analog/digital input data
plus
BK_LED_ERR_CODE (C 100,
I 1, A45) plus
BK_LED_ERR_ARG (C 100, I
1, A46) plus
Status (C 100, I 1 A 5) plus
DNS_i_Trmnldia
(C 100, I 1, A6) plus
BK_DIAG_VALUE
(C 100, I 1, A47)
13
specific
get/set
BK_SEL_STO
RED_POLL_C
_PATH
UINT
Power-up value for the receive
path. “Polled I/O” enumeration
for the assembly path, class and
instance for the I/O module
objects.
Notice: Only write values to this
attribute that are also available,
e.g., do not use analog inputs if
only digital input/output
modules are linked.