Table 82: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Description
14
specific
get/set
BK_SEL_STO
RED_COSCY
C_C_PATH
UINT
Power-up value for change of
state and cyclic connection.
Enumeration for the assembly
path, class and instance of the
I/O module objects.
Notice: Only write values to this
attribute that are also available,
e.g., do not use analog inputs if
only digital input/output
modules are linked.
15
specific
get/set
BK_EM_expe
cted_packet_rate
UINT
Defines the default time for the
explicit messaging connection
16
specific
get/set
BK_EM_watc
hdog_timeout_
action
USINT
Defines how
inactivity/watchdog explicit
messaging connection timeouts
are handled
17
specific
get/set
BK_PIO_expe
cted_packet_
rate
UINT
Defines the default time for the
poll I/O connection
18
specific
get/set
BK_PIO_watc
hdog_timeout_
action
USINT
Defines how
inactivity/watchdog poll
connection timeouts are handled
19
specific
get/set
BK_BS_expec
ted_packet_rate
UINT
Defines the default time for the
bit-strobe I/O connection
20
specific
get/set
BK_BS_watch
dog_timeout
_action
USINT
Defines how
inactivity/watchdog bit-strobe
I/O connection timeouts
are handled
21
specific
get/set
BK_COS_exp
ected_packet_
rate
UINT
Defines the default time for the
change of state and cyclic I/O
connection
22
specific
get/set
BK_COS_wat
chdog_timeout
_action
USINT
Defines how
inactivity/watchdog change
of state and cyclic I/O
connection timeouts
are handled
23
specific
get/set
BK_BOI
USINT
Defines the default value for
BIO (Obj. 0x03 Inst.1,
Att.3.) It handles the CAN-
Bus-Off situation
0: After detection of a bus-off
alarm, keep the CAN chip in the
Bus-Off (Reset) status
status.
1: If possible, full reset of the
CAN chip and after detection of
a bus-off alarm, continue with
communication.
24
specific
get/set
BK_DO_FAU
LT_REACTIO
N_ON_RELE
ASE_PIO
USINT
Defines the behavior after
allocation of the polled I/O
connection
0: No activity (default)
1: Error behavior processing for
fieldbus coupler/controller