126 I/O Modules
WAGO-I/O-SYSTEM 750
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
2-channel pulse width output module, 24 VDC
750-511 (and all versions)
In the input and output process image, pulse width output modules occupy 6 bytes
of user data: 4 data bytes and two additional control/status bytes. 6 bytes are
occupied in the process image.
Table 112: Input/Output Process Image, Pulse Width Output Modules
Input and Output Process Image
Instance
Byte designation
Remark
n
C0/S0
Control/status byte of channel 1
D0
Data value of channel 1
D1
n+1
C1/S1
Control/status byte of channel 2
D2
Counter setting value of channel 2
D3
These specialty modules represent 2 x 3 bytes and occupy 2 instances in class
(0x67) and 2 instances in class (0x68).
2-channel up/down counters
750-638, 753-638
In the input and output process image, counter modules occupy 6 bytes of user
data: 4 data bytes and two additional control/status bytes. The I/O module
provides 16-bit counter values for every counter. 6 bytes are occupied in the
process image.
Table 113: Input Process Image Counter Modules
Input Process Image
Instance
Byte designation
Remark
n
S0
Status byte of counter 1
D0
Counter value of counter 1
D1
n+1
S1
Status byte of counter 2
D2
Counter value of counter 2
D3
These specialty modules represent 2 x 3 bytes and occupy 2 instances in class
(0x67).