WAGO-I/O-SYSTEM 750
Device Description
45
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
4.4.2.2
Station address
The station address is set using slide switches 1 to 6.
The binary significance of the individual slide switches increases in the direction
of the slide switch numbers. Slide switch 1 is used to set the lowest bit with a
significance of 2
0
and slide switch 6 to set the highest bit with a significance of 2
5
.
If slide switch 1 is set to “ON”, “MAC ID” 1 is set, if slide switch 1 and 4 are set
to “ON”, “MAC ID” 9 is set ((2
0
+ 2
3
).
Station addresses in the range of 0 (all slide switches set to “OFF”) to 63 (all slide
switches set to “ON”) can be set for the DeviceNet
TM
fieldbus nodes. The station
address is set to 1 when delivered.
Example:
Setting the station address to 25.
-
ON
2
0
= 1
-
OFF
-
OFF
-
ON
2
3
= 8
-
ON
2
4
= 16
-
OFF
Figure 28: Example with Station Address Set to 25