116 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-306 DeviceNet
TM
Fieldbus Coupler
Manual
Version 2.0.0
10.1.5.2.1.10 Analog Input Point Object (0x67)
Instance 0
Table 92: Instance 0
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Value Description
1
required
get
Revision UINT
1
Revision number of the class
definition for the “Identity
Object”
2
optional
get
Max
instance
UINT
255
Maximum number of
instances of an object
generated at the time in this
class level of the device
Description of Instances
Table 93: Description of Instances
Instance ID Description
1
Reference to the first analog input point
2
Reference to the next analog input point
…
255
Reference to the last possible analog input point
Instance 1 … 255
Table 94: Instance 1
Attributes
ID
Utilization
in Device
Access
Rights
Name
Data Type Value
Description
1
Depending
on the type
of I/O
module
get
AIPOBJ_
VALUE
Array of
Byte
Current
Input
values
Input data
2
Dep. on
type
of module
get
AIPOBJ_
VALUE
USINT
No.
Bytes
Input data lengths
Services
Table 95: Service
Service
Code
Service Name
Description
0x0E
Get_Attribute_Single
Returns the content of a specific attribute
0x10
Set_Attribute_Single
Modifies the content of a specific attribute