8.2
Setting the DeviceNet
™
Station Address and Baud
Rate
1.
Switch off the power for the fieldbus coupler.
2.
Set the required DeviceNet
™
station address (“MAC ID”) using slide
switches 1 … 6 of the DIP switch.
3.
Set the required baud rate using slide switches 7 and 8.
Example:
Setting the station address “MAC ID” 4 (DIP 3 = ON) and baud rate 500 kBaud
(DIP 7 = OFF, DIP 8 = ON).
OFF
Station address
OFF
ON (2² = 4)
OFF
OFF
OFF
OFF
Baud rate
ON
Figure 40: Example of DIP Switch Settings
4.
Then switch on the supply voltage of the fieldbus coupler.
8.3
Configuring Static Assemblies
Configuring static assemblies is described in a separate document.
Please note Application Note A100103!
Configuring static assemblies is described in Application Note
A100103
.
The application note is available for download at the WAGO website