Reference Commands for Move Mode
•
173
Setpoint
commands
WAGO-I/O-SYSTEM 750
I/O Modules
3.2.4.1.10
STOP_NO_RAMP (0x19)
Sets the output frequency immediately to zero. Internal processing is
structured such that this command is given priority. All other commands are
discontinued immediately, in particular in the Mailbox mode. This command
has priority over STOP_FAST. This command is also initiated internally when
Enable has not been set.
Request
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
-
MB2
0x19
MB3 Reserved
MB4 Reserved
MB5 Reserved
Response
Byte 2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
MB0
0x40
MB1 T
Return
Code
MB2
0x19
MB3 Reserved
MB4 Reserved
MB5 Reserved