Overview of Error Blink Codes
•
213
Auxiliary
Commands
WAGO-I/O-SYSTEM 750
I/O Modules
Error
No.
Name
Description
Possible cause/Remedy
1551 MCALC_SPEED1 internal
internal
1552 MCALC_SPEED2 internal
internal
1553 MCALC_SPEED3 internal
internal
1554
MCALC_ACC1
During the ramp run at a
defined ramp time the
movement calculator has
determined partial
movement that exceeds
the internal value range
for acceleration
Adapt ramp time setting as
appropriate
1555
MCALC_ACC2
same as MCALC_ACC1 same as MCALC_ACC1
1556
MCALC_ACC3
During the ramp run at a
defined ramp path the
movement calculator has
determined partial
movement that exceeds
the internal value range
for acceleration
Adapt ramp path setting as
appropriate
1557 MCALC_PARA
The
movement
calculator has received
invalid parameters
Check all parameters;
Acceleration, moving
velocity, ramp time, ramp
path, ramp type, starting
position, target position
1561
MCALC_TIME1
Internal range exceeded
for moving time
internal *
1562 MCALC_TIME2
The
movement
calculator has
determined partial
movement that exceeds
the internal time range
(>500 h).
Check movement
parameters. This error
occurs on unrealistic
settings for velocity,
acceleration or positions.
With extreme parameters,
moving at the lowest
acceleration, for example,
yields a movement time that
far exceeds the internal
value range of 2^31ms.
1563
MCALC_TIME3
Internal range exceeded
for moving time
internal *
1564 MCALC_TIME4
The
movement
calculator has
determined a movement
sequence that exceeds
the internal time range
(>500 h).
Check movement
parameters. This error
occurs on unrealistic
settings for velocity,
acceleration or positions.
With extreme parameters,
moving at the lowest
acceleration, for example,
yields a movement time that
far exceeds the internal
value range of 2^31ms.