WAGO-I/O-SYSTEM 750
Commissioning 125
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
8.6
Restoring Factory Settings
For total deletion, first make a file system reset!
Note that you first reset the file system for the complete deletion of the controller.
Use for this the program “
WAGO Ethernet Settings
”, as described below, and
click first on the button
[Reset File System]
.
Then, you restore the factory settings.
To restore the factory settings, proceed as follows:
1.
Switch off the supply voltage of the fieldbus controller.
2.
Connect the communication cable 750-920 or 750-923 respectively the
Bluetooth
®
Adapter 750-921 to the service interface of the fieldbus
controller and to your computer.
3.
Switch on the supply voltage of the fieldbus controller.
4
Start the
WAGO-ETHERNET-Settings
program.
5.
In the top menu bar, select
[Factory Settings]
and click
[Yes]
to confirm.
A restart of the fieldbus node is implemented automatically. The start takes place
with the default settings.