WAGO-I/O-SYSTEM 750
System Description 33
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
3.6.4
Field Supply
3.6.4.1 Connection
Sensors and actuators can be directly connected to the relevant channel of the
I/O module in 1, 2, 3 or 4 conductor connection technology. The I/O module
supplies power to the sensors and actuators. The input and output drivers of
some I/O modules require the field side supply voltage.
The fieldbus coupler/controller provides field side power (DC 24 V). In this case it
is a passive power supply without protection equipment.
Power supply modules with or without fuse holder and diagnostic capability are
available for the power supply of other field potentials (DC 24 V, AC/DC 0 …
230 V, AC 120 V, AC 230 V). The power supply modules can also be used to set
up various potential groups. The connections are connected in pairs to a power
contact.
Figure 8: Field Supply for Standard Couplers/Controllers and Extended ECO Couplers
Table 6: Legend for Figure “Field Supply for Standard Couplers/Controllers and Extended ECO
Couplers”
Field supply
1 24 V (-15 % / +20 %)
2 0 V
3 Optional ground potential (functional earth)
Power jumper contacts
4 Potential distribution to adjacent I/O modules