WAGO-I/O-SYSTEM 750
Appendix 431
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
16.2.15 Modbus Group
The Modbus group contains information and settings about the controller's
modbus server.
Table 499: WAGO MIB – Modbus Group
Identifier
Entry
Access Description
1.3.6.1.4.1.13576.10.1.40.6.1
wioModbusTcp-
Enable
R/W Enable/disable the port of the Modbus
TCP server
0 = port of Modbus TCP server disable
1 = port of Modbus TCP server enable
Default value: { 1 }
1.3.6.1.4.1.13576.10.1.40.6.2
wioModbusUdb-
Enable
R/W Enable/disable the port of the Modbus
UDP server
0 = port of Modbus UDP server disable
1 = port of Modbus UDP server enable
Default value: { 1 }
1.3.6.1.4.1.13576.10.1.40.6.3
wioMax-
Connections
R/W The maximal count of modbus
connections
Default value: { 15 }
1.3.6.1.4.1.13576.10.1.40.6.4
wioConnection-
Timeout
R/W Timeout of the modbus connection
Default value: { 600 }
1.3.6.1.4.1.13576.10.1.40.6.5
wioModbus-
WatchdogMode
R/W Mode of the modbus watchdog
Default value: { 0 }
1.3.6.1.4.1.13576.10.1.40.6.6
wioModbus-
WatchdogTime
R/W Timeout of the modbus watchdog
Default value: { 100 }
1.3.6.1.4.1.13576.10.1.40.6.7
wioFreeModbus-
Sockets
R/W Unused and free modbus connections
Default value: { 15 }
1.3.6.1.4.1.13576.10.1.40.6.8
wioModbus-
ConnectionTable
-
1.3.6.1.4.1.13576.10.1.40.6.8.1
wioModbus-
ConnectionEntry
-
1.3.6.1.4.1.13576.10.1.40.6.8.1.1 wioModbus-
ConnectionIndex
R/W Index of modbus connection
1.3.6.1.4.1.13576.10.1.40.6.8.1.2 wioModbus-
ConnectionIp
R/W IP address of modbus connection
1.3.6.1.4.1.13576.10.1.40.6.8.1.3 wioModbus-
ConnectionPort
R/W Port of modbus connection