6 • The WAGO-I/O-SYSTEM 750
Installation
Modular I/O System
ETHERNET TCP/IP
2.2 Installation
2.2.1 Safty
notes
ESD (Electrostatic Discharge)
The modules are equipped with electronic components which may be de-
stroyed by electrostatic discharge.When handling the modules, ensure that the
environment (persons, workplace and packing) is well grounded. Avoid
touching conductive components, e.g. gold contacts.
Attention
Switch off the system prior to working on bus modules!
2.2.2 Mechanical
Installation
All system components can be snapped directly on a carrier rail in accordance
with the European standard EN 50022 (DIN 35).
Attention
Ensure that the carrier rail is fastened with countersunk head screws or blind
rivets as the snap-on foot of the I/O components extends onto the carrier rail.
The installation is simple and space saving. All modules have the same shape
to minimize the project commitment.
The reliable positioning and connection of the coupler and the individual I/O
modules is made using a tongue and groove system. Due to the automatic
locking, the individual components are securely seated on the rail after in-
stalling.