116 • I/O modules
Counter modules 750-404/000-005
Modular I/O System
ETHERNET TCP/IP
4.2.1.1.8 Variation
2 Channel Up Counter 16 Bit
750-404/000-005
Technical description
The mode described here is a 2 channel rising edge up counter 16 bit.
In this mode, the U/D input of module 750-404 is used for the clock input of
the second counter.
The following description is preliminary and is applicable to the factory confi-
guration.
The counter module can operate with all WAGO-I/O-SYSTEM bus-couplers
(except for the economy type).
Technical Data:
Item-No.:
750-404/000-005
Number of outputs
2
Output current
0.5 A
Number of counters
2
Input current (internal)
70 mA
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)
Signal voltage (0)
DC -3 V ... +5 V
Signal voltage (1)
DC + 15 V ... 30 V
Switching rate
5 kHz max.
(* 2 kHz when the U/D Input is dynamical switched)
Input current
5 mA typ.
Counter size
2x16 Bit Data
Isolation
500V System/power supply
Internal bit width
2x16 Bit Data; 8 Bit control/status
Configuration
none, or via software with the consent of WAGO
Operating temperature
0 °C ... + 55 °C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100, (*from upper edge of carrier rail)