I/O modules • 125
Digital Inputs 750-410, -411
Modular I/O System
ETHERNET TCP/IP
Technical Data:
Item-No.:
750-410*)
750-411*)
Number of inputs
2
Input filter
3 ms
0.2 ms
Voltage via power jumper contacts
DC 24 V (-15% / +20%)
Signal voltage (0)
DC -3 V...+5 V (std. EN 61131 Type 2)
Signal voltage (1)
DC 11 V...30 V (std. EN 61131 Type 2)
Input current (internal)
2.5 mA max.
Input current (field side)
8 mA typ.
Isolation
500 V System/power supply
Internal bit width
2
Configuration
no address or configuration adjustment
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
*) A 2-wire proximity switch can be connected, permissible closed-circuit cur-
rent
≤
2 mA