156 • I/O modules
Digital Outputs 750-514
Modular I/O System
ETHERNET TCP/IP
4.3.1.1.9 Digital Output Relay
(2 changeover contacts isolated outputs, AC 125 V, 0.5 A) 750-514
14 24
K1 K2
C
D
B
A
11 21
12 22
750-514
Power jumper contact
Data contacts
Relay 2
Status
Relay 1
Status
DO 2
L 2
DO 2
DO 1
L 1
DO 1
DO 2
N
N
Technical description
The power supply for the relay coils is not made through the power jumper
contacts but directly from the electronics. The respective output contacts of the
switching element are therefore always positioned at the field side.
These I/O modules are not provided with integrated power jumper contacts.
Care should be taken to supply each isolated module with separate power
supply connections.
A connection to ground is made through the series power jumper contact to a
power feed module.
The positions of the different modules in the configured station are the user’s
choice. A block type configuration is not necessary.
The output module can operate with all buscouplers of the
WAGO-I/O-SYSTEM.