184 • I/O modules
Analog Inputs 750-462, /000-XXX
Modular I/O System
ETHERNET TCP/IP
750-462/000-011, Type U -25°C -600°C
T[°C]
Value [hex]
Value [dec]
Status byte
[hex]
LED
<-25
<FF06
<-250
41
on
-25.0
FF06
-250
00
off
37.5
0177
375
00
off
100.0
03E8
1000
00
off
162.5
0659
1625
00
off
225.0
08CA
2250
00
off
287.5
0B3B
2875
00
off
350.0
0DAC
3500
00
off
412.5
101D
4125
00
off
475.0
128E
4750
00
off
537.5
14FF
5375
00
off
600.0
1770
6000
00
off
>600
1770
6000
42
on
No identification of open circuit, measuring value correspond to 0°C.
750-462/000-050, Type K without Cold junction compensation
T[°C]
Value [hex]
Value [dec]
Status byte
[hex]
LED
<-100
<FC18
<-1000
41
on
-100.0
FC18
-1000
00
off
0,0
0000
0
00
off
200.0
07D0
2000
00
off
350.0
0DAC
3500
00
off
500.0
1388
5000
00
off
650.0
1964
6500
00
off
800.0
1F40
8000
00
off
950.0
251C
9500
00
off
1100.0
2AF8
11000
00
off
1250.0
30D4
12500
00
off
1370.0
3584
13700
00
off
>1370
>3584
>13700
42
on
Open circuit
0000
0
0
off