I/O modules • 187
Analog Inputs 750-465, -466, (-486)
Modular I/O System
ETHERNET TCP/IP
The status of the input channels are indicated by the LEDs:
Function:
on
The channel function is error-free.
off
The communication to the bus coupler is broken.
Error:
on
The input signal is out of range < 3.5 mA
or > 20.5 mA.
off
The input signal is in range.
The input module can operate with all buscouplers of the
WAGO-I/O-SYSTEM (except for the economy type).
Technical Data:
Item-No.:
750-465,
750-465/000-200*
)
750-466,
750-466/000-200*
)
(formerly 750-486)
Number of inputs
2
Nominal voltage
via system voltage (DC / DC)
Input current (internal)
75 mA typ.
Input signal
0-20 mA
4-20 mA
Resistance
<150
Ω
at 20 mA
Resolution
12 Bit
(*
)
12 Bit + sign for the variations
750-465/000-200 and 750-466/000-200)
Signal voltage
29 V max.
Current limiting
< 40 mA typ. at 24 V for 1 min
Measuring error
< ± 0,3% (from upper limit of effective range)
Isolation
500V System/power supply
Conversion time
2 ms typ.
Bit width per channel
16 Bit: Data
8 Bit: Control/Status, optional
Configuration
none, or via software with the consent of WAGO
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)