I/O modules • 191
Analog Inputs 750-467, (-487)
Modular I/O System
ETHERNET TCP/IP
Technical Data:
Item-No.:
750-467,
750-467/000-200*
)
Number of inputs
2
Nominal voltage
via system voltage
Input current (internal)
60 mA
Overvoltage protection
35 V max.
Input signal
0-10 V
Resistance
133 k
Ω
typ.
Resolution
12 Bit
(*
)
12 Bit + sign for the variations 750-467/000-200)
Isolation
500V System/power supply
Conversion time
2 ms typ.
Bit width per channel
16 Bit: Data; optional 8 Bit: Control/Status
Configuration
none, or via software with the consent of WAGO
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
Numerical format
All analog values will be shown in a unit numerical format. The resolution is
12 Bits.
The following table will explain the numerical format. The 3 LSBs are not si-
gnificant.