192 • I/O modules
Analog Inputs 750-467, (-487)
Modular I/O System
ETHERNET TCP/IP
750-467
Input voltage
0-10V
Value
Binary
Hex.
Dec.
Status
> 10
0111 1111 1111 1111
7F FF
32767
42
10
0111 1111 1111 1XXX
7F F8
32760
0
5
0100 0000 0000 0XXX
40 00
16384
0
2.5
0010 0000 0000 0XXX
20 00
8192
0
1.25
0001 0000 0000 0XXX
10 00
4096
0
0.0781
0000 0001 0000 0XXX
01 00
256
0
0.0049
0000 0000 0001 0XXX
00 10
16
0
0.0024
0000 0000 0000 1XXX
00 08
8
0
0
0000 0000 0000 0XXX
00 07
7
0
0
0000 0000 0000 0XXX
0
0
0
Numerical format for Siemens function blocks
For fieldbus masters with the ability to evaluate the status information within
the data word, i.e. Siemens format
The status information is contained in Bit B0 .. B2.
The digitized input is placed at the position Bit B3 .. B15.
750-467/000-200
Input voltage
0-10V
Value
Binary
X E O
*)
Hex.
Dec.
Status
>10
0101 0000 0000 0
0 0 1
50 01
20481
42
10
0101 0000 0000 0
0 0 0
50 00
20480
0
5
0011 0000 0000 0
0 0 0
30 00
12288
0
2.5
0010 0000 0000 0
0 0 0
20 00
8192
0
1.25
0001 1000 0000 0
0 0 0
18 00
6144
0
0.0049
0001 0000 0000 1
0 0 0
10 08
4104
0
0
0001 0000 0000 0
0 0 0
10 00
4096
0
*)
X : without meaning, E : short circuit or open circuit, O : overflow
Status byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Error
x
x
x
x
Overrange
x