I/O modules • 203
Analog Inputs 750-472, -474
Modular I/O System
ETHERNET TCP/IP
4.4.1.1.9 2 Channel Analog Inputs
(0-20mA / 4-20mA single-ended) 750-472, -474
E1 E2
13 14
C
D
B
A
+ +
0V 0V
S S
750-472
AI 2
Power jumper contacts
Data contacts
Function AI 2
24V
0V
Function AI 1
AI 1
Error AI 2
Error AI 1
Shield
(screen)
Shield
(screen)
I/O modules and variations
Item-No.:
Name:
750-472
2AI 0-20mA 16 Bit s.e.
750-472/000-200
2AI 0-20mA 16 Bit s.e. S5-463
750-474
2AI 4-20mA 16 Bit s.e.
750-474/000-200
2AI 4-20mA 16 Bit s.e. S5-460 /465
Technical description
This description is only intended for hardware and software version X X X X
0 2 0 2- - -- 0 5 0 3.
The serial number can be found on the right side of the module.
The input channels are single ended and they have a common ground potential.
The inputs are connected to +I. Via 24 V / 0 V power can be provided directly
to the sensor from the module. Power connections are made automatically
from module to module through the PJC when snapped onto the DIN rail.
The shield is connected to "S". The connection is made automatically when
snapped onto the DIN rail.
The input module can operate with all buscouplers of the
WAGO-I/O-SYSTEM
(except for the economy type).