210 • I/O modules
Analog Outputs 750-550, -556, (-580)
Modular I/O System
ETHERNET TCP/IP
4.5.1.1.1 2 Channel Analog Outputs
(DC 0-10V /
±
10V)
750-550, -556, (-580)
A1 A2
13 14
C
D
B
A
M M
S S
750-550
AO 2
Data contacts
Function AO 2
Function AO 1
AO 1
Shield
(screen)
Shield
(screen)
Common
(ground)
Common
(ground)
I/O modules and variations
Item-No.:
Description
Name
750-550
2 Channel Analog Output, 0-10V
2AO 0-10V DC
750-550/000-200
formerly 750-580
2 Channel Analog Output, 0-10V
with status infomation within the
data word
2AO 0-10V DC Siemens Format
750-556
2 Channel Analog Output,
±
10V
2AO ±10V DC
750-556/000-200 2 Channel Analog Output,
±
10V
with status infomation within the
data word
2AO ±10V DC Siemens Format
Technical description
This description is only intended for hardware version X X X X 2 A 0 1 - - - -.
The serial number can be found on the right side of the module.
The output signal of 750-550 is a 0-10 V signal, the output signal of 750-556
is a
±
10 V signal.
Sensors should be connected to "O" and to the common ground.
The shield is connected to "S". The connection is made automatically when
snapped onto the DIN rail.
These I/O modules are not provided with integrated power jumper contacts.
The power supply is made by the data contacts with a DC-DC converter.
The output module can operate with all buscouplers of the
WAGO-I/O-SYSTEM (except for the economy type)
.