212 • I/O modules
Analog Outputs 750-550, -556, (-580)
Modular I/O System
ETHERNET TCP/IP
750-556
Output voltage
±10V
Value
Binary
Hex.
Dec.
10
0111 1111 1111 1111
7F FF
32767
5
0100 0000 0000 0000
40 00
16384
2.5
0010 0000 0000 0000
20 00
8192
1.25
0001 0000 0000 0000
10 00
4096
0.0781
0000 0001 0000 0000
01 00
256
0.0049
0000 0000 0001 0000
00 10
16
0
0000 0000 0000 1111
00 0F
15
0
0000 0000 0000 0000
00 00
0
-2.5
1110 0000 0000 0000
E0 00
57344
-5
1100 0000 0000 0000
C0 00
49152
-7.5
1010 0000 0000 0000
A0 00
40960
-10
1000 0000 0000 0000
80 00
32768
Numerical format for Siemens function blocks
For fieldbus masters with the ability to evaluate the status information within
the data word, i.e. Siemens format.
The status information is contained in Bit B2 .. B0.
The digitized input is placed at the position Bit B3 .. B15.