214 • I/O modules
Analog Outputs 750-552, -554, (-584)
Modular I/O System
ETHERNET TCP/IP
4.5.1.1.2 2 Channel Analog Outputs
(0-20mA / 4-20mA)
750-552, -554, (-584)
A1 A2
13 14
C
D
B
A
+ +
0V 0V
S S
750-552
AO 2
Power jumper contacts
Data contacts
Function AO 2
24V
0V
Function AO 1
AO 1
Shield
(screen)
Shield
(screen)
I/O modules and variations
Item-No.:
Description
Name
750-552
2 Channel Analog Output, 0-20 mA
2AO 0-20mA
750-552/000-200
2 Channel Analog Output, 0-20 mA
with status infomation within the data word
2AO 0-20mA
(Siemens Format)
750-554
2 Channel Analog Output, 4-20 mA
2AO 4-20mA
750-554/000-200
formerly 750-584
2 Channel Analog Output, 4-20 mA
with status infomation within the data word
2AO 4-20mA
(Siemens Format)
Technical description
This description is only intended for hardware version X X X X 2 A 0 1 - - - -.
The serial number can be found on the right side of the module.
The output signal of 750-552 and 750-554 is a 0-20 mA or 4-20 mA signal.
Sensors may be connected to "O" and to the common ground (0V).
The shield is connected to "S". The connection is made automatically when
snapped onto the DIN rail.
Power connections are made from module to module via power jumper con-
tacts when snapped onto the DIN rail.
For a self-supporting function, the power supply has to be connected by an in-
put module (i.e. 750-602).
The output module can operate with all buscouplers of the
WAGO-I/O-SYSTEM (except for the economy type)
.