I/O modules
Supply modules 750-601, -609, -615 • 219
Modular I/O System
ETHERNET TCP/IP
4.6.1.1.2 Supply
modules
(DC 24V / AC 230V / AC 120V)
750-601, -609, -615
+ +
-
-
13 14
B
A
750-601
T 6,3 A
250 V
0V
Power jumper contacts
Status
voltage supply
Supply via
power jumper contacts
24V
Data contacts
Error
fuse blown
Technical description
The supply module feeds field power through the power jumper contacts. Ma-
ximum current supply to the modules with fuse holder is 6.3 A. Should more
current be needed, additional supply modules may be added in the assembly.
The modules 750-601, 609 and 615 are additionally equipped with a fuse.
Changing the fuse is accomplished by pulling out the fuse holder and remo-
ving the fuse.
A blown fuse is indicated by a red LED.
Make sure the proper voltage is applied to the supply module. Use caution
when changing voltage potential within a node. All modules following the
supply module will be powered at the new potential. The following table
shows the voltage ratings for the supply modules.
Technical Data:
Item-No.:
750-601
750-609
750-615
Voltage
DC 24 V
AC 230 V
AC 120 V
Current via contacts
max. 6.3 A
Fuse
5 x 20, 6.3 A
Operating temperature
0 °C ... + 55 °C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64 x 100, (from upper edge of carrier rail)