80
•
Fieldbus controller 750-842
Starting up ETHERNET TCP/IP fieldbus nodes
Modular I/O System
ETHERNET TCP/IP
Example: ping 10.1.254.202
Fig. 3-33: Example for the function test of a fieldbus node
P012910e
3.
When the Return key has been pressed, your PC will receive a response from
the controller, which will then be displayed in the DOS prompt.
If the error message: "Timeout" appears instead, please compare your entries
again to the allocated IP address and check all conections.
4.
Also note that the TXD/RXD light will flash verifying each response
5.
When the test has been performed successfully, you can close the DOS prompt.
The network node has now been prepared for communication.
3.2.6.6
Viewing the HTML pages
The information saved in the fieldbus controller can be viewed as an HTML
page using a web browser.
•
Information on the fieldbus node (Terminal Status):
-
Number of digital, analog or complex modules and their model numbers
-
Representation of the process image
•
Information on the fieldbus controller (Controller and Network Details):
-
Order number
-
Firmware version
-
MAC-ID
-
IP address
-
Gateway address (if applicable)
-
Subnet mask
-
Number of transmitted and received packets
•
Diagnostic information on the fieldbus controller (Controller Status):
-
Error code
-
Error argument
-
Error description
Fig. 3-34: Viewing the information through the HTTP protocol
G012916d