WAGO-I/O-SYSTEM 750
Device Description
19
750-476 2AI ±10V DC S.E.
Manual
Version 1.1.0
Pos: 31 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/CAGE CLAMP-Anschlüsse - Überschrift 3 @ 6\mod_1256296337770_21.docx @ 43674 @ 3 @ 1
3.2.3
CAGE CLAMP
®
Connectors
Pos: 32 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Anschlüsse/Analogeingangsklemmen/Anschlüsse 750-0472, -0474, -476 @ 20\mod_1407249401134_21.docx @ 161193 @ @ 1
Figure 4: CAGE CLAMP
®
Connectors
Table 5: Legend for Figure “CAGE CLAMP
®
Connectors”
Channel
Designation
Connection Function
1
AI 1
1
Current signal
24 V
2
Field supply U
v
0 V
3
Field supply 0 V
S
4
Shield
2
AI 2
5
Current signal
24 V
6
Field supply U
v
0 V
7
Field supply 0 V
S
8
Shield
Pos: 33 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Hinweis/Hinweis: Geschirmte Signalleitungen verwenden! @ 7\mod_1265723251019_21.docx @ 50140 @ @ 1
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
Pos: 34 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1