WAGO-I/O-SYSTEM 750
Appendix 129
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
•
Length of the output process image [byte]
Figure 46: GSD/GSE – Extended configuration record
Parameter "Port x > Multiplier cycle time"
The cycle time multiplier is used to calculate the master cycle time. The
adjustable number range reaches from 0 to 63.
Parameter "Port x > Master cycle time"
The master cycle time is calculated as follows:
Table 127: PROFIBUS DP/V1, calculation of the master cycle time
Master cycle time
Unit
Multiplier * 0.1
ms
6.4 + multiplier * 0.4
ms
32.0 + multiplier * 1.6
ms
Parameter "Port x > Operating mode"
This parameter is used to set the operating mode of a port.
Table 128: PROFIBUS DP/V1, operating mode
Operating Modes
Inactive
DI (Digital Input)
DO (Digital Output)
IO-Link