134 Appendix
WAGO-I/O-SYSTEM
750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Table 133: PROFIBUS event codes
PROFIBUS DP
Channel Diagnostics
IOL
event
code
Meaning
Solution
IOL type IOL mode
Error code Error text
0x5011 Loss of volatile
memory contents
Check the batteries Error
coming/
going
9 Error
0x5012 Weak
batteries
Replace
the batteries Warning coming/
going
17 Warning
0x5013
…
0x50FF
Reserved -
-
-
-
-
0x5100 General
power
supply error
Check availability
Error
coming/
going
17 No
field
voltage
0x5101 Blown fuse or no
fuse
Replace the fuse
Error
coming/
going
18 Fuse
defective
0x5102
…
0x510F
Reserved -
-
-
-
-
0x5110 Allowable
primary
power supply
exceeded
Check the tolerance
of the power supply
Warning coming/
going
3 Over-
voltage
0x5111 Allowable
primary
power supply not
met
Check the tolerance
of the power supply
Warning coming/
going
2 Over-
voltage
0x5112 Secondary
power
supply error
Check the tolerance
of the power supply
Warning coming/
going
17 Warning
0x5113
…
0x5FFF
Reserved -
-
-
-
-
0x6000 Device
software
faulty
Check the firmware
version used
Error coming/
going
9 Error
0x6001
…
0x630F
Reserved -
-
-
-
-
0x6310 Record:
Parameter
loss
coming/
going
16 Configu-
ration
error
0x6001
…
0x631F
Reserved -
-
-
-
-
0x6320 Record:
Configuration error
Use the manual to
check the
configuration
Error coming/
going
16 Configu-
ration
error
0x6321 Missing
configuration
Use the manual to
check the
configuration
Error coming/
going
15 Parame-
ter
missing
0x6322
…
0x634F
Reserved -
-
-
-
-
0x6350 Parameterization
change
Check the
configuration
Error coming/
going
9 Error
0x6351
…
0x76FF
Reserved -
-
-
-
-
0x7700 Line break in a
subordinate device
Check the wiring
Error
coming/
going
6 Line
break