138 Appendix
WAGO-I/O-SYSTEM
750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Table 133: PROFIBUS event codes
PROFIBUS DP
Channel Diagnostics
IOL
event
code
Meaning
Solution
IOL type IOL mode
Error code Error text
0x8CC4
...
0x8CC5
Manufacturer
specific
- -
-
-
-
0x8CC6 The frequency of the
events or with which
the events are
written to the queue
is higher than the
readout frequency of
the queue. The
oldest events are
overwritten and are
thus lost.
Prevent events.
Error
coming/
going
9 Error
0x8CC7 1. IOL device,
whose process data
length is greater than
the segmentation set,
is connected.
2. Segmentation is
set smaller than the
process data length
of the attached IOL
device.
3. The SIO byte and
port-specific
segmentation have a
length of 0 byte and
the port is in the DI,
DO or SIO state.
Following solutions:
1. Set segmentation
to available process
data length.
2. Set segmentation
to available process
data length.
3. SIO byte must
have a length of 1
byte or segmentation
must be set to the
process data length.
Warning once
-
-
0x8CC8
…
0x8DFF
Manufacturer
specific
- -
-
-
-
0x8E00
…
0xAFFF
Reserved -
-
-
-
-
0xB000
…
0xBFFF
Reserved for
profiles
- -
-
-
-
0xC000
…
0xFEFF
Reserved -
-
-
-
-
0xFF00
…
0xFFFF
SCSI-specific event
codes