28
Device Description
WAGO-I/O-SYSTEM 750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Do not create a negative voltage on C/Q!
Do not create a negative voltage between L- and C/Q because this can cause the
destruction of the IO-Link master.
Note the minimum cable cross-section!
Maintain the recommended minimum cable cross-section:
For 20 m cable length, select a minimum cross-section of 0.34 mm².
You can use unshielded cable.
Use binary sensors with PNO or push/pull output!
Binary sensors with PNP output or push/pull output can be connected to an IO-
Link master in operating modes "DI" and "DO", but not connected to an NPN
output.