WAGO-I/O-SYSTEM 750
Configuration and Parameterization
57
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
9.1.1.4
Register “Port Configuration“
The setting options in the "Port Configuration" tab are identical for all ports. The
tabs at the top of the window are used to switch between ports 1 to 4.
One IODD (description files standardized by the manufacturer), which contains
the available parameters of the IO-Link, can be assigned to each of the 4 ports and
each attached IO-Link device.
Save IODD files in a specific directory!
So that IODD files are displayed under "Port Configuration", save them in the
following path:
For Windows XP:
C:\Documents and Settings\All Users\Common Files\WAGO Software
For Windows 7:
C:\Users\Public\Documents\WAGO Software
Only assign the IODD when the IO-Link master is not connected!
If the IO-Link master is connected, i.e. the
[Connect]
button is active in the
toolbar, the IODD cannot be selected.
Disconnecting the IO-Link master enables the drop-down field to select the
IODD.
Click the
[Read]
button in the toolbar to read the respective port configuration.