60
Configuration and Parameterization
WAGO-I/O-SYSTEM 750
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Table 27: Register “Port Configuration”
Option
Description
Inspector Level
The "Inspector Level" indicates which parameters of an attached IO-Link device have to match
those of the current port configuration to be recognized as valid.
No Check
Whether the parameters match is not checked. A device
is always recognized as valid (for this part).
Compatible
The following fields of the attached IO-Link device
have to match those of the port configuration: Device
ID, Vendor ID.
Type Related
Identical
The following fields of the attached IO-Link device
have to match those of the port configuration: Device
ID, Vendor ID and Serial Number. A unique device
serial number is required for valid device recognition.
Process Image related
No Check
Whether the parameters match is not checked. A device
is always recognized as valid (for this part).
PD
Length
Strict
The lengths for the process input and output data of an
IO-Link device have to match those saved in the I/O
module. Otherwise, the device is classified as invalid.
PD
Length
Loose
The process data lengths of the IO-Link master must be
equal to or smaller than the buffer size, which provides
the I/O module for the IO-Link device.
Parameter Server Mode Enable
Parameter
Server
Parameter server enabled (factory setting)
Disable
Parameter
Server
Parameter server disabled
Disable
Upload
Prevents parameter upload:
The upload request of the IO-Link device is suppressed
by the I/O module.
Disable
Download
Prevents parameter download:
The download request of the control is not sent to the
IO-Link device by the I/O module.
Comparable Data
"Comparable Data" describes data of the devices attached to the ports.
This data is only needed for validation when starting a device.
Revision ID
Version number of the SDCI protocol, which is supported by the IO-
Link device.
Vendor ID 1
Manufacturer ID of the attached device (top byte)
Vendor ID 2
Manufacturer ID of the attached device (bottom byte)
Device ID 1
Device ID of the attached device (top byte)
Device ID 2
Device ID of the attached device (middle byte)
Device ID 3
Device ID of the attached device (bottom byte)
In PD Length
Size and structure of the process input data of the IO-Link device
Out PD Length
Size and structure of the process output data of the IO-Link device
Serial No.
Unique serial number of the attached device
[Get Data]
Reads the current data of the device attached to the port