WAGO-I/O-SYSTEM 750
Configuration and Parameterization
61
750-657 IO-Link Master
Manual
Version 1.0.2, valid from FW/HW-Version 02/01
Application parameter upload:
The IOL-D parameters are uploaded to the parameter server of the IO-Link master
if the device parameters have been changed.
This occurs either "remotely" via the bus or "locally" on the device.
Application parameter download:
When uploading to the IO-Link device, the master checks the identity of the
device. (DeviceID, VendorID, SerialNumber).
When successful, the parameter server synchronizes the parameters:
•
For devices without ISDU support, parameters are always downloaded.
•
For devices with ISDU support, parameters are only downloaded if the
checksums do not equal the parameter sets.